Model: PG-2000
pg2000capum45.DOC Rev: 4.5
- 5 -
1.3 SPECIFICATIONS
OPERATION
The CAP can access a maximum of 80 EC Gold transmitters assigned to up
to 8 zones and set Sensor Fault, High-High, High, and Low alarms based on
ppm values read from the transmitters. In addition, the maximum and
average ppm values are reflected on two optional 4-20mA outputs per zone.
USER INTERFACE
Calibration and setup 4 Line x 20 char LCD and 4X4 membrane keypad.
Network RS-485 Modbus protocol connection to EC Gold sensors. Optional additional
serial port to link to a Building Automation System.
OUTPUTS
Alarms Differential threshold Low, High, and High-High alarms per zone for up to 8
zones. Up to 4 gases are supported with independent Low, High, and High-
High alarms for each gas type. Common Sensor Fault alarm
Relay Contacts 4 Relays integral relays and up to 16 external relays in banks of 8. Each bank
of 8 is accessible via RS-485 and may be located where convenient to save
on wiring. Each relay may be field linked to any combination of 24 alarm
sources: High-High, High and Low alarms per zone for up to 8 zones. Relay1
may be designated as a System Fault alarm. Contacts are SPDT
10A/120VAC.
Alarm Delay Independent Delay to On and Delay for each relay. Delay range: 0-100
minutes field adjustable.
Buzzer Activated by any zone’s High-High alarm with acknowledge input. Each bank
of 8 relays also includes a buzzer and acknowledge input.
4-20mA Outputs Optional. May be ordered in place of enclosure mounted buzzer or as a 4-20
mA output boards. Output boards are accessible via RS-485 and may be
located where convenient. 2 mA outputs per zone indicating max. ppm and
average ppm.
ELECTRICAL SPECIFICATION
Base Scanner Unit
Power 120VAC / 230VAC / 24VDC ±10% (specify at time of order), 15VA max.
Fuse T160mA, 250VAC. Note: For 24VDC power input, the fuse is a 5mm x 20mm,
1/2A, Fast Blow type. This fuse is installed within the unit and must be
installed by qualified personnel only.
The equipment belongs to Pollution Degree2, Installation category II
Power from Scanner panel to EC Gold Transmitters
Power 24VDC / current depends on number of transmitters.
MECHANICAL SPECIFICATIONS
Enclosure Nema 1 or 4X (optional) wall mount with clear cover to protect keypad / LCD
Dimensions 305mm (12") H, x 305mm (12") W x 101.5mm (4") D or
356mm (14") H, x 305mm (12") W x 203mm (8") D (Fiberglass)
Weight PG-2000 (fiberglass) 6.25 kg (13.75lbs)
PG-2000 (Nema 1) 7.18 kg (15.8lbs)
ENVIRONMENTAL SPECIFICATIONS
Operating Temp. 0 - 55 Deg. C
Relative Humidity 90% max. with no condensation.